BENKA fire cables offer high fire resistance, maintain circuit integrity, and support alarms, emergency lighting and critical communications with minimal smoke and no acidic gases.
| Conductor | Stranded bare copper conductor to IEC 60228, DIN VDE 0295, EN 60228, class 2/class 5 |
| Fire barrier | Mica tape outside each core/all cores + fiberglass tape (optional) |
| Insulation | Cross-linked LSZH (HX)/Cross-linked polyethylene (XLPE) |
| Outer sheath | Low smoke zero halogen (LSZH) compound. Color: Orange, RAL 2003 |
| Working voltage | 600/1000V |
| Test voltage | 3500V |
| Rated temperature | -20°C to +90°C |
| Flame retardant | IEC 60332-1 |
| Flame propagation | IEC 60332-3-22 |
| Fire resistant | IEC 60331-21,DIN 4102-12 (210) & EN 50020 Annex E |
| Halogen free | IEC 60754-1 |
| Acid and corrosive gases | IEC 60754-2 |
| Smoke density | IEC 61034-2 |
| Standard & Approval | RoHS, SIRIM,TUV |
| Minimum bending radius | 8 x OD (static) |
@ Bản quyền thuộc về Châu Duy Phát